详细信息
您现在的位置:首页 > 产品展示

Series
HY inverters
Control Mode
SPWM
Input Power
380V class:380±15%;230V class:220±15%
5-Digits Display & Status Indicator Lamp
Displaying frequency, current, revolution, voltage, counter, temperature, FOR or REV rotation, and fault, etc.
Communication Control
RS-485
Working Temperature
-10~40℃
Humidity
0-95% Relative Humidity(without dew)
Vibration
Below 0.5G
Frequency Control
Range
0.1~2500.0Hz
Accuracy
Digital: 0.1%(-10~40℃); Analog: 0.1% (25±10℃)
Setting Resolution
Digital: 0.1Hz; Analog: 1‰ of max. Operating frequency
Output Resolution
0.1Hz
Operator Setting Method
Press directly ← ∧ ∨ to set.
Analog Setting Method
External Voltage 0-5V,0-10V,4-20mA,0-20mA.
Other Functions
Frequency lower limit, starting frequency, stopping frequency, three skip frequencies can be respectively set.
General Control
Ramp Control
Selectable 4-speed steps ramp-up and -down time (0.1-6500s).
V/F Curve
Set V/F curve at will.
Torque Control
Torque increase settable by max. 10.0%. The starting torque can reach 150% at 1.0Hz.
Multi-Inputs
6 multi-function input terminals for 8–speed steps control, program operation, switching of 4-speed Ramp, UP/DOWN function, counter, external emergency stop and other functions.
Multi-Outputs
5 multi-output for displaying of running, zero speed, counter, external abnormity, program operation and other information and warnings.
Other Functions
Auto Voltage Regulation(AVR), Decelerating Stop or Coasting Stop, DC Braking, Auto Reset and Restart, Frequency Track, PLC Program Control, Traverse Control, Drawing Control、Auto Energy Saving, Carrier Adjustable (Up to 20KHz), etc.
Protection Functions
Overload Protection
Electronic relay protection motor drive
Drive(for constant torque  150%/1 min. for the kinds of fan 120%/1min.)
Fuse Protection
When the fuse breaks , the motor will stop.
Over-voltage
220V class:DC Voltage >400V
380V class:DC Voltage >800V
Under-voltage
220V class:DC Voltage <200V
380V class:DC Voltage <400V
Restart After Instant Stop
Restart with Frequency Track after Instant Stop
Stall Protection
Stall protection in ramp operation
Output Short Circuit
Electrical circuit protection
Other Functions
Fin over-heat protection, restriction of reverse running, direct start after power on, fault reset, parameter lock PID, one-drive-more, etc.

 

 